Removal of External Deposits on Boiler Tubes

Authors

  • C. P. De Naval Chemical and Metallurgical Laboratory, Bombay
  • J. C. Chaudhuri Naval Chemical and Metallurgical Laboratory, Bombay
  • K. P. Buch Naval Chemical and Metallurgical Laboratory, Bombay
  • A. K. Audi Naval Chemical and Metallurgical Laboratory, Bombay

DOI:

https://doi.org/10.14429/dsj.20.6154

Keywords:

Vanadium pentoxide, IN ship, Starboard boilers

Abstract

The superheater tubes in Port and Starboard boilers were found to have completely clogged by heavy deposits, which on analysis mainly vanadium pentoxide and sodium sulphmatter. The cleaning of the deposits was accomplished by alternate spraying with 15-20 per cent hydrogen peroxide and washing with hot water jets. Over the past two years, since the date of cleaning, the IN ship is operating without any trouble in the boilers.

Downloads

Published

2014-07-01

How to Cite

De, C. P., Chaudhuri, J. C., Buch, K. P., & Audi, A. K. (2014). Removal of External Deposits on Boiler Tubes. Defence Science Journal, 20(3), 195–200. https://doi.org/10.14429/dsj.20.6154